Deluge control unit "KSD pilot". KMU universal diaphragm valve type Universal diaphragm valve KSD type kmu

KSD 100/1.2 K-UU.01

KSD 150/1.2 K-UU.01

GOST R 51052-97

Description

Designed for launching fire extinguishing liquid in stationary automatic installations water-foam fire extinguishing of deluge and sprinkler versions and the issuance of a control pulse to the pressure indicator. Operating temperature range from plus 4 to 50°С.

Specifications

Parameter name

KSD-100

KSD-150

Conditional passage, mm

Working pressure (Рр), MPa:

Minimum

Maximum

Actuation pressure of the incentive chamber of the valve (Рс=0.2Рр), MPa:

Minimum

Maximum

Locking pressure of the incentive chamber of the valve (Рz=Рс+0.5Рр), MPa:

Minimum

Maximum

Response time (at minimum operating pressure), s

Nominal flow, l/min

Head loss coefficient (e), m

Weight, kg, no more

Assigned service life, years, not less

0,14

1,20

0,028

0,24

0,098

0,30

0,4+0,1

2200

0,002

0,14

1,20

0,028

0,24

0,098

0,30

0,4+0,1

5000

0,0006

1 - body,

2 - cover,

3 - membrane,

4 - support disk,

6 - cover,

7 - hairpin,

8 - nut,

9 - gasket,

10 - sealing ring,

11 - hairpin,

12 - nut,

13 - cover,

14 - membrane,

15 - saddle.

Name

Dimensions

Weight,

kg

D

KSD-100

180+ 0,8

8 +0,52

KSD-150

240+ 0,6

8 +0,52

The valves are supplied as part of control units and are pressure-tested to a pressure of 1.6 MPa.

Scheme of KSD valve operation

A - valve inlet

B - valve outlet

B - supra-membrane cavity of the working chamber

G - submembrane cavity of the working chamber

D, E - cavities of the incentive chamber

MR - membrane of the working chamber

MP - incentive chamber membrane

RD - pressure indicator

"D" - drainage hole

"P" - working hole

"C" - signal hole

"K" - control hole

"P" - incentive hole

Device and principle of operation:

The MP membrane divides the working chamber of the valve into two cavities C and D.

The MP membrane divides the valve incentive chamber into two cavities D and E.

The cavity B of the valve is connected by a channel with the cavity D and the working hole P, designed to be connected to the supply pipeline to fill them with a working medium and create pressure in them.

The cavity D is connected by channels with the cavity G and the signal hole "C" intended for connection of the signaling device and the drainage line. The cavity E through the channel in the cover is connected with the incentive hole "P", designed to feed the incentive line through the throttling hole. Drain hole "D", located in the cavity of the outlet B, is designed to quickly drain the fluid during maintenance. Control hole "K" located in the cavity of the outlet B, intended for connection with the drainage line in deluge installations (eliminates accumulation of liquid at the valve outlet due to possible leaks), and for connection with the impelling hole "P" in sprinkler installations.

To bring the valve to its original state (standby mode), it is necessary to create pressure in the cavity E and the incentive line through the hole "P" from the line that feeds the incentive line. Then through the hole "P" it is necessary to create pressure in the cavity B from the supply pipeline that feeds the fire extinguishing installation. After the gate valve 3D is opened at the valve inlet, it is ready for operation, while the MP membrane, acting through the stem on the gate, closes the inlet A, and the MP membrane, under pressure in cavity E, closes the channels connecting cavity D with cavities C and D.

When the stimulus device is triggered by the impact of the fire, the cavity E communicates through the hole "P" with the atmosphere. The pressure in cavity E drops. Under the pressure of the fluid flowing from the cavity B into the cavity D, the MP membrane closes the holes "P", turning off the feed of the incentive line, and connects the cavities D, C and G to each other. The pressure in cavities C and D equalizes and ensures the opening of the shutter due to the movement of the MP membrane under the action of the pressure of the fire extinguishing liquid at the valve inlet. The signal about the actuation of the valve is given by means of a pressure sensor RD type SDU-M, connected to the signal hole "C".

To use the valve in deluge installations, it is necessary to connect hole "P" to the incentive line, and hole "K" to the drainage line. To use the valve in sprinkler installations, holes "P" and "K" must be connected to each other. Depending on the operating conditions, liquid or air can be used as a medium for supplying the incentive line.

Article: no

Price:
88 831 rub.

Qty:

Deluge control unit PILOT KSD for DN 100 mm- normally closed locking device, designed for operation in control units of water and foam fire extinguishing installations, supplies fire extinguishing agent. The valve can be used in deluge systems with hydraulic and electric drive, and their combinations.

When using the appropriate piping, the PILOT KSD valve at DN 100 ensures the activation of a fire alarm when the system is triggered. The diaphragm mechanism ensures even distribution of pressure on the obturator area, prevents excessive deformation of the diaphragm and ensures a longer service life.

The deluge valve PILOT KSD for DN 100 is actuated by liquid pressure in the supply pipeline. The damper complies with the climatic version O location category 4 for operation with the lower temperature limit of + 4°C in accordance with GOST 15150-69.

A polyurethane powder coating is used for corrosion protection.

For proper operation of the valve in fire extinguishing installations, it is recommended to familiarize yourself with GOST R 51052-2002 "Automatic water and foam fire extinguishing installations. Control units. General technical requirements. Test methods" and with the set of rules SP 5.13130-2009 "Fire protection systems. Fire alarm and fire extinguishing installations are automatic. Norms and rules of design».

Example symbol deluge valve DN 100 according to GOST R 51052-2002: KSD 100 / 1.6 (G0.08) - F.O4 - "PILOT KSD".

Material specification

Working temperature: +4 oС - +80 oС.
Service life before repair - not less than 5 years.

Principle of operation:

The main parts of the valve are the body, the diaphragm and the bonnet. The membrane with the lid forms a shut-off chamber "ЗК", having a connection port "З" on the lid. The body edge in contact with the membrane separates the flow part into the inlet "B" and outlet "P" cavities. The outlet cavity has a port “D” on the body for connecting a drain and a port “C” for connecting a signaling device.
The valve can be in standby mode (closed) and in working mode (supply of fire extinguishing agent). The valve is put into standby mode when fluid is supplied under pressure to the locking chamber "ZK", while the membrane is pressed against the edge of the housing 1 and blocks the communication of the cavities "B" and "P".

In the operating mode, the liquid from the locking chamber is discharged through the stimulating device (manual start-up valve, solenoid valve, etc.) into the drain. The pressure in the locking chamber "ZK" becomes less than in the inlet cavity "B", as a result of which the membrane opens the passage of liquid into the outlet cavity "P" and further into the supply pipeline of the installation.

Safety requirements

Work related to the installation and operation of the valve must be carried out by personnel who have the right to work with products of pipeline fittings operating under pressure, who have studied this passport and in compliance with the requirements of GOST 12.2.003-91. Routine work with disassembly and assembly of the valve must be carried out in the absence of pressure.

Technical specifications:

Mounting:

1. Close the shutter (valve) on the supply pipeline and the manual start valve.
2. Open the drain cock and water supply valve to the shut-off chamber, leave for a while so that the shut-off chamber fills with water and builds up excess pressure in it. While filling the chamber through
solenoid valve for 2-5 seconds, water can flow out.
3. Open the manual start valve to bleed air from the shut-off chamber, close the manual valve slowly after the water flows out in a dense stream without the presence of air bubbles.
4. Check all connections for leakage, to do this, close the water supply valve to the shut-off chamber and observe the pressure gauge, visually inspect all connections. If the pressure gauge
do not change, then slowly open the water supply valve to the shut-off chamber.
5. Slowly open the shutter (valve) on the inlet pipeline and make sure that there is no water leakage through the drain cock (there may be a slight discharge of water for a short time).
6. Fully open the shutter (valve) on the inlet pipeline, close the drain cock.
7. The valve is ready for operation.

Maintenance:

In order to carry out timely Maintenance valve should:
- Conduct a daily visual inspection for the presence and magnitude of pressure on the pressure gauge, the absence of leaks.
- Quarterly check the condition and tightness of fasteners.
When carrying out routine maintenance of the fire extinguishing installation, disconnect the valve from the system, relieve pressure with a manual start valve and clean the filter and compensator; remove the cover, membrane,
remove dirt, check the condition of parts, repair damage if necessary, assemble the valve in its original state.

Equipment:

Delivery set (pcs.): Valve PILOT KSD - 1; compensator - 1; check valve - 1; filter - 1; tap for supplying water to the locking chamber - 1; manual start valve - 1; Solenoid valve - 1; pressure gauge - 1; drain valve - 1;
pressure alarm must be ordered separately.

Manufacturer's Warranty:

The manufacturer guarantees that the valve complies with the requirements of DIA 634269.10.000 TU, subject to the conditions of transportation, storage, installation and operation.
The warranty period is 1 year.

Rice. 2. Schematic diagram of the electrically driven strapping

Rice. 3. Overall and connecting dimensions

Doo L H B Weight, kg A, mm D, mm FROM strapping Drainage
50 191 99 125 4 - - - ½” ¾”
65 290 181 181 10 145 19 4 ½” 1¼”
80 310 200 200 17,5 160 19 8 ½” 1¼”
100 350 230 230 25,5 180 19 8 ½” 2”
150 480 300 302 36 240 23 8 ½” 2”
200 600 389 354 71 295 23 12 ½” 2”

Rice. 4. Graph of the dependence of nominal pressure losses on water flow


Price:
from: before:

Name:

Vendor code:

Text:

Select a category:
All Primary fire extinguishing agents » Powder fire extinguishers » Carbon dioxide fire extinguishers » Knapsack fire extinguishers » Air-foam fire extinguishers » Self-acting fire extinguishers » Brackets and fastenings for fire extinguishers » Sleeve branchings » Foam generators, foam mixers, hydraulic elevators » Latex fire hoses » Fire hoses "Sibteks" for fire hydrants » Fire hoses "Armtex" » Suction hoses » Spray barrels » Fire monitors » Fire heads connecting » Fire hydrants » Fire hydrant valves » Fire blankets and felt mats » Fire columns » In-house fire extinguishing devices » Fire extinguisher for extinguishing pyrotechnic products FIREOFF Fire cabinets, shields, stands, doors, hatches » Hinged metal fire hydrant cabinets » Metal built-in fire hydrant cabinets » In-house fire extinguishing cabinets » Fire extinguisher cabinets » Stands for fire extinguishers » COMBI fire stands » Sand boxes » Fire doors » Manholes fire-fighting » Fire fighting equipment (Crowbar, hook, buckets, shovels) » Fire shields of open type » Fire shields of closed type » Housekeepers » Ballot boxes Fire automatics » Sprinkler fire extinguishing systems »» Viking equipment »» TYCO equipment Shut-off valves by Dinansi »» Shut-off valves by Tecofi »» Pressure switches and flow switches »» Corrugated pipes, fittings, KOFULSO piping »» Equipment by Chang Der Fire Protections Corp (Taiwan) »» ​​Aqua-Gefest equipment »» DINARM equipment »» Non-welded coupling joints » » Fire Force equipment »» Other manufacturers of sprinkler equipment » Foam fire extinguishing systems »» Equipment for foam systems by K.S.A. »» Foam fire extinguishing equipment Chang Der Fire Protections Corp (Taiwan) »» ​​Foam fire extinguishing equipment Spetsavtomatika »» Uralmechanika foam equipment » Powder fire extinguishing systems »» Powder fire extinguishing equipment GARANT »» AUPP ORION »» Powder fire extinguishing modules MPP TUNGUS » Novec gas fire extinguishing systems 1230 » Waste removal fire extinguishing systems » Gas fire extinguishing modules » Automatic water feeders » Hydropneumatic tanks » Restaurant and kitchen fire extinguishing system ANSUL R-102 » Smoke removal systems » Fire alarm systems »» BOLID equipment »» Protectowire thermal cable »» Protectowire thermal cable accessories »» Thermal cable IPLT » Aerosol fire extinguishing pump equipment» Koshin motor pumps » Robin motor pumps » Aquarius motor pumps » PN-40 UV centrifugal fire pump » GRUNDFOS pumps » WILO pumps » NTsPN normal pressure fire pumps » Fire pumps high pressure MNPV and NCPV emergency situations» Holmatro universal spreaders » Holmatro cullet » Holmatro stabilization and fastening equipment » Cordless combi tools » Combination tools » Hydraulic jacks » Holmatro manual pumps » Emergency pumping stations Holmatro » RECCO R-9 search system in avalanche zones " Equipment for maintenance of fire brigades » Equipment for maintenance of fire hoses » Module for drying clothes of firefighters » Installation for testing the strength of fire escapes » Equipment for maintenance of fire extinguishers » Stand for drying, disinfection and storage of breathing apparatus » Installation for applying water fire-bioprotective compositions » Device for testing roof fencing » Mobile fire station PPMP (set) » Equipment for completing fire stations Machinery and special equipment » Forest fire plows and equipment for fighting forest fires fire-fighting module) » Fire-fighting tank trucks » Forest fire tractors Occupational safety and health equipment » Respiratory protection equipment »» Civilian gas masks »» Industrial gas masks »» Insulating gas masks »» Accessories for gas masks, boxes, masks, bags, flasks »» Self-rescuers »» Containers for storing self-rescuers »» Protective chambers for children (KZD) »» Respirators »» Breathing apparatus »» Components and equipment for breathing apparatus »» Degassing equipment »» Cabinets for storing gas masks »» Protective hoods » First aid equipment first aid»» First-aid kits for institutions and industries, automotive »» First-aid kits for household use »» First-aid kits for civil defense »» Hydrogel products »» Dressings »» Stretchers »» Rescue covers »» Other medical products » Head protection equipment » Eye protection equipment » Protective clothing »» Clothing for protection against chemical and bacteriological effects »» Fire-resistant capes »» Fighting clothing for firefighters » Hearing protection » Hand protection » Fencing » Scaffolding » Dielectric products » Communication equipment (Radio sets) »» Radio stations Motorola »» Vertex Standard radios »» ICOM radios »» Kenwood radios »» Alinco radios »» Roger radios »» Midland radios »» ARGUT radios »» ENTEL radios »» Hytera radios »» Antennas for base radios »» Antennas for car radios »» Power meters and SWR »» Repeaters (repeaters), amplifiers »» RF coaxial cable »» Radio modems »» Power supplies and voltage converters » Lighting equipment »» Ecoton flashlights »» Headlights and searchlights »» Laser flashlights »» EagleTac tactical and battery flashlights »» Fenix ​​LED rechargeable flashlights »» Thrunite LED flashlights »» Heavy-duty professional Polarion flashlights »» JetBeam tactical LED flashlights »» NiteCore LED heavy-duty flashlights »» Ecoton flashlight accessories »» Laser pointers »» Chemical light sources »» Lupine flashlights » Thermal imagers »» Fluke thermal imagers »» Pulsar Quantum thermal imagers » Night vision devices (NVD) ) » Binoculars »» BPC, BKFTs and BPO binoculars »» Yukon binoculars »» PENTAX binoculars »» CARL ZEISS binoculars »» Leica binoculars »» Leupold binoculars »» Olympus binoculars »» Bushnell binoculars »» Minox binoculars ) » Loudspeakers (Megaphones) » Autonomous heat sources » Gas detectors » Dosimetric control devices » Quadcopters, drones and UAVs » Aro Handheld Metal Detectors » Hand Held Metal Detectors

Description

Characteristics

Documentation

PURPOSE

The deluge valve PILOT KSD with a hydraulic membrane drive is a normally closed locking device, used to operate in the control units of water and foam fire extinguishing installations, and supplies a fire extinguishing agent. The valve can be used in sprinkler air control units and deluge units with hydraulic, electric, pneumatic actuators and their combinations. When using the appropriate piping, the PILOT KSD valve provides a fire alarm when the system is triggered.
The diaphragm mechanism guarantees even distribution of pressure on the obturator area, prevents excessive deformation of the diaphragm and ensures a longer service life.
The valve is actuated by the pressure of the fluid in the supply line.


For proper operation of the valve in fire extinguishing installations, it is recommended to familiarize yourself with GOST R 51052-2002 "Automatic water and foam fire extinguishing installations. Control units. General technical requirements. Test methods" and with the set of rules SP 5.13130-2009 "Fire protection systems. Fire alarm and fire extinguishing installations are automatic. Norms and rules of design».
An example of a symbol for a valve DN 100 according to GOST R 51052-2002: KSD 100 / 1.6 (G0.08) - F.O4 - “PILOT KSD”.

VALVE OPERATION

The main parts of the valve are the body, the diaphragm and the bonnet (fig. 1 of the technical description). The membrane with the lid forms a shut-off chamber "ЗК", having a connection port "З" on the lid. The body edge in contact with the membrane separates the flow part into the inlet "B" and outlet "P" cavities. The outlet cavity has a port “D” on the body for connecting a drain and a port “C” for connecting a signaling device.
The valve can be in standby (closed) and operating (supply of fire extinguishing agent) modes. The valve is put into standby mode when fluid is supplied under pressure to the locking chamber "ZK", while the membrane is pressed against the edge of the housing 1 and blocks the communication of the cavities "B" and "P".
In the operating mode, the liquid from the locking chamber is discharged through an incentive device (manual start-up valve, solenoid valve, etc.) into the drain. The pressure in the locking chamber becomes less than in the inlet cavity "B", as a result of which the membrane opens the passage of liquid to the outlet cavity "P" and further to the supply pipeline of the installation.

CONTENTS OF DELIVERY

Delivery set (pcs.): Valve PILOT KSD - 1; compensator - 1; check valve - 1; filter - 1; tap for supplying water to the locking chamber - 1; manual start valve - 1; Solenoid valve - 1; pressure gauge - 2; drain valve - 1;

You can download 3D models of equipment for the REVIT program in rfa format, you can in the "download" section

TECHNICAL SPECIFICATIONS
produced diameters (DN mm): 50, 65, 80, 100, 150, 200

Operating pressure range MPa: 0.15-1.6

Working temperature: +4 oС - +80 oС.

Starting element B (solenoid): 24V, 220V (specify voltage when ordering)

Response time no more than s: 2

Weight not more than kg: Du50-4kg, Du65-10kg, Du80-17.5kg, Du100-25.5kg, Du150-36kg, Du200-71kg

Service life not less: 10 years

The design of the valve is shown in fig. 1.Technical description

Overall and connecting dimensions are shown in fig. 3

The damper complies with the climatic version O location category 4 for operation with the lower temperature limit of + 4°C in accordance with GOST 15150-69.
A polyurethane powder coating is used for corrosion protection.

An example of a symbol for a valve DN 100 according to GOST R 51052-2002: KSD 100 / 1.6 (G0.08) - F.O4 - “PILOT KSD”.

CONTENTS OF DELIVERY
Delivery set (pcs.): Valve PILOT KSD - 1; compensator - 1; check valve - 1; filter - 1; water tap
in the locking chamber - 1; manual start valve - 1; Solenoid valve - 1; pressure gauge - 2; drain valve - 1;
pressure switch to be ordered separately

CERTIFICATION
Certificate of compliance with the technical regulation on fire safety requirements: C-RU.PB97.V.00790 (until 06/29/2022).